CVE Intelligence

Vulnerabilidades do Hitachi Energy RTU500 series CMU firmware

🔔 Criar alerta RSS Verificador de versão

CVEs publicadas que afetam Hitachi Energy RTU500 series CMU firmware: 7 registro(s), com versões afetadas e correções.

CVE-2026-8067 Média · 6.5 CWE-862 29/09/2026
Missing Authorization em Hitachi Energy RTU500 series CMU firmware
An improper authorization vulnerability in the end-of-life versions of RTU500’s web application allows an authenticated user to trigger the RTU500 to reboot through the reset endpoint. Successful exploitation could cause temporary device unavailability and disruption of its intended operation.
CVE-2026-8066 Crítica · 9.1 CWE-23 29/09/2026
Relative Path Traversal em Hitachi Energy RTU500 series CMU firmware
A directory traversal vulnerability in the file upload functionality of Hitachi Energy RTU500 end-of-life versions allows an unauthenticated attacker to write or overwrite arbitrary files on the device file system. Depending on the files affected, successful exploitation could result in unauthorized modification of device data or disruption of the device’s intended operation.
CVE-2026-8065 Crítica · 9.1 Exploit público CWE-306 29/09/2026
Missing Authentication for Critical Function em Hitachi Energy RTU500 series CMU firmware
An authentication bypass vulnerability in the firmware update endpoint of Hitachi Energy RTU500 end-of-life versions allows an unauthenticated attacker to upload arbitrary firmware through a crafted POST request. Successful exploitation could allow the attacker to modify device functionality or compromise the integrity or availability of the device.
CVE-2026-17539 Média · 5.9 CWE-476 03/09/2026
NULL Pointer Dereference em Hitachi Energy RTU500 series CMU firmware
RTU500 has a vulnerability, where high-load scenarios, such as sending GI requests at short intervals, may cause a NULL pointer dereference in the last entry of the enhanced message queue. This can cause a BCI_IEC104 fatal write error, resulting in connection interruption and restart, and ultimately a denial of service for bidirectional IEC 60870-5-104 communication.
CVE-2026-8479 Média · 6.9 CWE-476 26/05/2026
NULL Pointer Dereference em Hitachi Energy RTU500 series CMU firmware
IEC 60870-5-104 used in bidirectional mode in RTU500 is vulnerable for a NULL pointer dereferencing, if a specially crafted sequence of messages is sent for a certain time, causing Denial of Service impact. Product is only affected if IEC 60870-5-104 functionality in bidirectional mode (BCI) is configured.
CVE-2026-1773 Alta · 7.5 CWE-184 24/02/2026
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of…
IEC 60870-5-104 used in RTU500: Potential Denial of Service impact on reception of invalid U-format frame. Product is only affected if IEC 60870-5-104 bi-directional functionality is configured. Enabling secure communication following IEC 62351-3 does not remediate the vulnerability but mitigates the risk of exploitation.
CVE-2026-1772 Média · 5.3 CWE-280 24/02/2026
RTU500 web interface: An unprivileged user can read user management information. The…
RTU500 web interface: An unprivileged user can read user management information. The information cannot be accessed via the RTU500 web user interface but requires further tools like browser development utilities to access them without required privileges.