Vulnerabilidades do Phoenix Contact VPLCNEXT CONTROL 3000
🔔 Criar alerta RSS Verificador de versão
CVEs publicadas que afetam Phoenix Contact VPLCNEXT CONTROL 3000: 5 registro(s), com versões afetadas e correções.
CVE-2025-41771
Média · 4.3
CWE-89 12/08/2026
SQL injection
An authenticated attacker with low privileges can access an endpoint in the controller’s web interface that is vulnerable to SQL injection. The vulnerability affects a SQLite database used only for storing notification messages. Therefore, the impact is limited to the system’s notification functionality.
CVE-2025-41770
Alta · 7.5
CWE-770 12/08/2026
Unauthenticated Denial of Service
An unauthenticated denial-of-service vulnerability in the device's PLCnext Engineer communication interface allow an remote attacker to interrupt access via the client application. Successful exploitation prevents communication until the PLCnext service is manually restarted.
CVE-2025-41769
Crítica · 9.8
CWE-120 12/08/2026
Unauthenticated Buffer Overflow in PROFINET Service
The device's PROFINET service is affected by a buffer overflow vulnerability that exists in the default configuration. An unauthenticated remote attacker could exploit this vulnerability to reboot the device or execute arbitrary code.
CVE-2025-41670
Alta · 7.8
CWE-427 27/05/2026
Untrusted Search Path
A local user with low privileges may be able to influence the behavior of a privileged system service by manipulating configuration or application-related files located in user-writable areas of the filesystem. The affected service processes data from locations that are not sufficiently protected against modification by low-privileged users. As the service runs with elevated privileges, successful exploitation may result in a local privilege escalation.
CVE-2025-41669
Alta · 8.8
CWE-347 27/05/2026
Insufficient Verification of Data Authenticity
The Web-based Management allows a remote low privileged Engineer user to install additional APPs on the device downloaded from the PLCnext Store without implementing any data verification mechanism, leading to the capability for an Engineer user to reach arbitrary code execution with root privileges on the PLC device. A successful exploitation may allow to install a manipulated APP package, potentially impacting integrity and availability of the PLCnext Control.