CVE-2011-20002
Alta · 7.4
CWE-294 14/10/2025
Authentication Bypass by Capture-replay em Siemens SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants)
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
CVE-2011-20001
Alta · 7.5
CWE-20 14/10/2025
Improper Input Validation em Siemens SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants)
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.3), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.3). The web server interface of affected devices improperly processes incoming malformed HTTP traffic at high rate. This could allow an unauthenticated remote attacker to force the device entering the stop/defect state, thus creating a denial of service condition.