CVE Intelligence

Vulnerabilidades de Schneider Electric

🔔 Criar alerta RSS

CVEs publicadas que afetam produtos de Schneider Electric: 35 registro(s), com severidade, exploração e correções.

Somente exploradas (KEV) →

CVE-2026-102250 Alta · 8.6 CWE-345 13/10/2026
Insufficient Verification of Data Authenticity em Schneider Electric Sage RTU 1410
CWE-345: Insufficient Verification of Data Authenticity vulnerability exists that could allow modified firmware to be uploaded when an authorized admin user begins a firmware update procedure which could result in control over the device.
CVE-2026-9718 Média · 6.5 CWE-617 25/06/2026
CWE-617 Reachable Assertion vulnerability exists that could allow an authenticated…
CWE-617 Reachable Assertion vulnerability exists that could allow an authenticated attacker to trigger a denial-of-service condition, impacting system availability when a specially crafted request is sent to a vulnerable network-exposed service.
CVE-2026-9717 Alta · 7.2 CWE-78 25/06/2026
OS Command Injection em Schneider Electric Powerlogic P7 Firmware
CWE-78 Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could allow unauthorized execution of commands with elevated privileges, impacting system integrity, confidentiality, and availability when a privileged authenticated user interacts with a vulnerable network-exposed service.
CVE-2026-9716 Alta · 7.5 CWE-476 25/06/2026
NULL Pointer Dereference em Schneider Electric Powerlogic P7 Firmware
CWE-476 NULL Pointer Dereference vulnerability exists that could cause a denial-of-service condition, rendering the device’s HMI and configuration functionality unavailable when malformed requests are received over exposed network interfaces.
CVE-2026-9651 Média · 4.4 CWE-732 25/06/2026
Incorrect Permission Assignment for Critical Resource em Schneider Electric Easylogic T150 Firmware
CWE-732 Incorrect Permission Assignment for Critical Resource vulnerability that could cause unauthorized disclosure of password hashes and potential account compromise when an attacker with privileged local access reads improperly protected system files.
CVE-2026-9650 Alta · 7.5 CWE-522 25/06/2026
Insufficiently Protected Credentials em Schneider Electric Easylogic T150 Firmware
CWE-522 Insufficiently Protected Credentials vulnerability that could cause unauthorized access and exposure of sensitive information when unauthenticated attacker accesses credentials stored within firmware or system files. With this credential an attacker could subsequently compromise the device if they have physical access to the device.
CVE-2026-8045 Média · 6.5 CWE-611 09/06/2026
XML External Entity (XXE) em Schneider Electric Struxureware Data Center Expert
CWE-611 Improper Restriction of XML External Entity Reference vulnerability exists that could cause information disclosure of server-side file contents when an attacker with a Data Center Expert user account submits crafted XML payloads to SOAP service endpoints.
CVE-2026-6332 Alta · 7.5 CWE-312 14/05/2026
Clear Text Storage of Sensitive Information on EcoStruxure™ Machine Expert HVAC
CWE-312: Cleartext Storage of Sensitive Information vulnerability exists that could cause the disclosure of a sensitive information which could result in revealing protected source code and loss of confidentiality, When an authorized attacker accesses the source code for editing or compiling it.
CVE-2026-6866 Alta · 7.5 CWE-1188 12/05/2026
Initialization of a Resource with an Insecure Default vulnerability on EcoStruxure™ Panel Server
CWE-1188 Initialization of a Resource with an Insecure Default vulnerability exists that could cause unauthorized disclosure of sensitive information when credentials revert to initial settings in rare circumstances, enabling unauthorized authentication using known credentials.
CVE-2026-6865 Alta · 7.1 CWE-22 12/05/2026
Improper Limitation of a Pathname to a Restricted Directory Vulnerability on Multiple Products
CWE-22: Improper Limitation of a Pathname to a Restricted Directory (“Path Traversal”) vulnerability that could cause unauthorized access to sensitive files when user-supplied input is improperly handled during server-side file path processing.
CVE-2026-4827 Alta · 8.7 CWE-331 12/05/2026
Insufficient Entropy vulnerability on Multiple Products
CWE‑331: Insufficient Entropy vulnerability exists that could lead to unauthorized access when an attacker on the network can exploit weaknesses in session‑management protections.
CVE-2026-4832 Média · 6.9 CWE-798 14/04/2026
Use of Hard-coded Credentials em Schneider Electric Easergy MiCOM P14x
CWE-798 Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to sensitive device information when an unauthenticated attacker is able to interrogate the SNMP port.
CVE-2026-2405 Média · 6.5 CWE-400 14/04/2026
Uncontrolled Resource Consumption em Schneider Electric Powerchute Serial Shutdown
CWE-400 Uncontrolled Resource Consumption vulnerability exists that could cause excessive troubleshooting zip file creation and denial of service when a Web Admin user floods the system with POST /helpabout requests.
CVE-2026-2404 Média · 5.3 CWE-116 14/04/2026
Improper Encoding or Escaping of Output em Schneider Electric Powerchute Serial Shutdown
CWE-116 Improper Encoding or Escaping of Output vulnerability exists that could cause log injection and forged log when an attacker alters the POST /j_security check request payload.
CVE-2026-2403 Média · 4.3 CWE-1284 14/04/2026
CWE-1284 Improper Validation of Specified Quantity in Input vulnerability exists that…
CWE-1284 Improper Validation of Specified Quantity in Input vulnerability exists that could cause Event and Data Log truncation impacting log integrity when a Web Admin user alters the POST /logsettings request payload.
CVE-2026-2402 Média · 5.3 CWE-307 14/04/2026
Improper Restriction of Excessive Authentication Attempts em Schneider Electric Powerchute Serial Shutdown
CWE-307 Improper Restriction of Excessive Authentication Attempts vulnerability exists that would allow an attacker to gain access to the user account by performing an arbitrary number of authentication attempts with different credentials on a sequence of requests to multiple endpoints.
CVE-2026-2401 Média · 5.0 CWE-532 14/04/2026
Insertion of Sensitive Information into Log File em Schneider Electric Powerchute Serial Shutdown
CWE-532 Insertion of Sensitive Information into Log File vulnerability exists that could cause confidential information to be exposed when a Web Admin user executes a malicious file provided by an attacker.
CVE-2026-2400 Média · 4.3 CWE-93 14/04/2026
CWE-93 Improper Neutralization of CRLF Sequences ('CRLF Injection') vulnerability exists…
CWE-93 Improper Neutralization of CRLF Sequences ('CRLF Injection') vulnerability exists that could cause application user credentials to reset when a Web Admin user alters the POST /setPCBEDesc request payload.
CVE-2026-2399 Média · 6.1 CWE-22 14/04/2026
Path Traversal em Schneider Electric Powerchute Serial Shutdown
CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal') vulnerability exists that could cause critical files overwritten with text data when a Web Admin user alters the POST /REST/upssleep request payload.
CVE-2026-2273 Alta · 8.2 CWE-94 10/03/2026
Code Injection em Schneider Electric Ecostruxure Automation Expert
CWE-94: Improper Control of Generation of Code ('Code Injection') vulnerability exist that could cause execution of untrusted commands on the engineering workstation which could result in a limited compromise of the workstation and a potential loss of Confidentiality, Integrity and Availability of the subsequent system when an authenticated user opens a malicious project file.
CVE-2026-1286 Média · 6.5 CWE-502 10/03/2026
Deserialization of Untrusted Data em Schneider Electric Ecostruxure Foxboro Dcs Control Software
CWE-502: Deserialization of untrusted data vulnerability exists that could lead to loss of confidentiality, integrity and potential remote code execution on workstation when an admin authenticated user opens a malicious project file.
CVE-2025-13957 Alta · 7.5 CWE-798 10/03/2026
Use of Hard-coded Credentials em Schneider Electric EcoStruxure™ IT Data Center Expert (Formerly known as StruxureWare Data Center Expert)
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause information disclosure and remote code execution when SOCKS Proxy is enabled, and administrator credentials and PostgreSQL database credentials are known. SOCKS Proxy is disabled by default.
CVE-2025-13902 Média · 5.4 CWE-79 10/03/2026
Cross-site Scripting (XSS) em Schneider Electric Modicon M258 Firmware
CWE-79 Improper Neutralization of Input During Web Page Generation ('Cross-site Scripting') vulnerability exists that could cause condition where authenticated attackers can have a victim’s browser run arbitrary JavaScript when the victim hovers over a maliciously crafted element on a web server containing the injected payload.
CVE-2025-13901 Média · 5.3 CWE-404 10/03/2026
Improper Resource Shutdown or Release em Schneider Electric Modicon M241 Firmware
CWE-404 Improper Resource Shutdown or Release vulnerability exists that could cause partial Denial of Service on Machine Expert protocol when an unauthenticated attacker sends malicious payload to occupy active communication channels.
CVE-2025-11739 Alta · 7.8 CWE-502 10/03/2026
Deserialization of Untrusted Data em Schneider Electric Ecostruxure Power Monitoring Expert
CWE‑502: Deserialization of Untrusted Data vulnerability exists that could cause arbitrary code execution with administrative privileges when a locally authenticated attacker sends a crafted data stream, triggering unsafe deserialization.