CVE Intelligence

MZ Automation Lib60870 vulnerabilities

🔔 Create alert RSS Version checker

Published CVEs affecting MZ Automation Lib60870: 3 record(s), with affected versions and fixes.

CVE-2026-63033 Medium · 6.5 CWE-125 Jul 30, 2026
MZ Automation lib60870 Out-of-bounds Read
A crafted IEC 60870-5-104 I-frame with a declared object count exceeding what fits in the ASDU body causes InformationObject_ParseObjectAddress to read one byte past the end of the heap-allocated message buffer.
CVE-2026-61893 Medium · 6.5 CWE-125 Jul 30, 2026
MZ Automation lib60870 Out-of-bounds Read
A crafted IEC 60870-5-104 I-frame with TypeID 104 (C_TS_NA_1) and an inflated object count causes TestCommand_getFromBuffer to read one byte past the end of the heap-allocated message buffer.
CVE-2026-16002 High · 8.2 CWE-125 Jul 23, 2026
Out-of-bounds Read in MZ Automation lib60870
The affected product is vulnerable to an Out-of-bounds read, which may allow an attacker to crash the parsing process and cause a denial of service.